NORD Drivesystems BU0750 User Manual

Page 122

Advertising
background image

NORDAC SK 750E Manual

122

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P715

Enablement time

Always visible

0.0 ... 9999 h

This parameter shows the time for which the FI was enabled and supplied current to the output.

P716

Actual frequency

Always visible

-400.0 ... 400.0 Hz

Displays the actual output frequency.

P717

Actual rotation speed

Always visible

-9999...9999 rpm

Displays the actual motor speed calculated by the FI.

P718

... - 01

... - 02

... - 03

Actual setpoint frequency

Always visible

-400.0 ... 400.0 Hz

Displays the frequency specified by the setpoint. (see also 10.1 Setpoint processing)

... - 01 = Actual setpoint frequency from the setpoint source

... - 02 = Actual setpoint frequency after processing in the FI status machine

... - 03 = Actual setpoint frequency after frequency ramp

P719

Actual current

Always visible

0.0 ... 500.0 A

Displays the actual output current.

P720

Actual torque current

Always visible

-500.0 ... 500.0 A

Displays the actual calculated torque-developing output current. The basis for calculation are
the motor data P201 ... P209.

-500.0 ... 500.0 A

negative values = generator, positive values = motor.

P721

Actual field current

Always visible

-500.0 ... 500.0 A

Displays the actual calculated field current. The basis for calculation are the motor data P201 ...
P209.

P722

Actual voltage

Always visible

0 ... 500 V

Displays the actual AC voltage supplied by the FI output.

P723

Actual voltage component U

d

Always visible

-500 ... 500 V

Displays the actual field voltage component.

P724

Actual voltage component U

q

Always visible

-500 ... 500 V

Displays the actual torque voltage component.

P725

Actual cos

Always visible

0.00 ... 1.00

Displays the actual calculated power factor of the drive.

P726

Apparent power

Always visible

0.00 ... 300.00 kVA

Displays the actual calculated apparent power. The basis for calculation are the motor data
P201 ... P209.

P727

Effective power

Always visible

0.00... 300.00 kW

Displays the actual calculated effective power. The basis for calculation are the motor data

P201 …P209.

P728

Mains voltage

Always visible

0 ... 1000 V

Displays the actual mains voltage at the FI input.

P729

Torque

Always visible

-400 ... 400 %

Displays the actual calculated torque. The basis for calculation are the motor data P201 ...
P209.

Advertising