3.3.3 Customer unit Basic I/O

(SK CU1-BSC, Part No.: 278200000)

The (Customer Unit) I/O provides sufficient control terminals for
simple control tasks and is therefore an economic solution for
many applications.
There are 1 analog input and 3 digital inputs available for control
of the frequency inverter. The analog differential input can
process positive signals of 0...10V.
By means of a relay contact, brake control can be actuated or
warnings can be sent to another system. A total of 13 different
relay functions are available.
The digital inputs of the Basic I/O can also be assigned analog
functions (see process controller, Section 10.3). Here, input
voltages ≥10V are processed as 10V signals and correspond to
100% (9V = 90%, ... , 0V=0%).

Connector

Functions

Maximum cross-section

Parameter

X3.1

Output relay

1.5 mm

2

P434 ... P436

X3.2

Analog input

1.5 mm

2

P400 ... P408

X3.3

Digital inputs

1.5 mm

2

P420 ... P422
























NOTE: All control voltages are based on a common reference potential!

Potentials AGND /0V and GND /0V are internally linked in the device.

The maximum total current 5/15V is 300mA!

Floating contacts or
output of a PLC: 7.5...33V

(low = 0...3.5Volt)

Differential input

0...10 V

X

3

.1

X

3

.2

X

3

.3

01 REL1.1

02 REL1.2

11 VREF 10V

12 AGND /0V

13 AIN1 -

14 AIN1 +

21 DIG IN 1

22 DIG IN 2

23 DIG IN 3

42 VO +15V

Digital inputs:

DIG IN 1 = On right

DIG IN 2 = On left

DIG IN 3 = Parameter set bit 0

Output relay:
max. 2.0A
28V DC /230 V AC

U

REF

= 10 V / I

max

= 10 mA

0V, gnd

Voltage supply:
15V, max. 300mA

Analog PLC output: 0...10V
or potentiometer: 2...10k