7.9 Information

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P700

Actual error

Always visible

0.0 ... 20.9

Actual error present. Further details in Section 8

Error messages

.

ControlBox:

Descriptions of the individual error numbers can be found under Error
Messages.

ParameterBox: Errors are displayed in plain text, further information can be found under Error

Messages.

P701

.. - 01

...

.. - 05

Last fault 1...5

Always visible

0.0 ... 20.9

This parameter stores the last 5 faults. Further details in Section 8

Error messages

.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.

P702

.. - 01

...

.. - 05

Freq. previous fault 1...5

Always visible

-400.0 ... 400.0 Hz

This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.

P703

.. - 01

...

.. - 05

Current, previous fault 1...5

Always visible

0.0 ... 500.0 A

This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.

P704

.. - 01

...

.. - 05

Voltage, previous fault 1...5

Always visible

0 ... 500 V AC

This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.

P705

.. - 01

...

.. - 05

UZW, previous fault 1...5

Always visible

0 ... 1000 V DC

This parameter stores the link voltage that was being delivered at the time the error occurred.
The values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.