NORD Drivesystems BU0750 User Manual

Page 106

Advertising
background image

NORDAC SK 750E Manual

106

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter set Available with option

P434

Function relay 1

P

BSC

STD

MLT

BUS

0 ... 38
[ 1 ]

Control terminals 1/2: Settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay contact closes
(Function 11 opens) when the limit value is reached and opens (function 11 closes) when a 10%
smaller value is undershot. This behaviour can be inverted with a negative value in P435.

Setting / Function

Digital Output ... for limit

value or function

(see also P435)

0 = No function

open

1 = External brake, to control a mechanical brake on the motor. The

relay switches at a programmed absolute minimum frequency
(P505). For typical brakes a setpoint delay of 0.

2 … 0.3 seconds

(see also P107) should be programmed.
A mechanical brake can be directly AC switched. (Please note the
technical specifications of the relay contacts)

Closes

2 = Inverter operating, the closed relay contact indicates voltage FI

output (U - V - W).

Closes

3 = Current limit, based on the setting of the motor rated current in

P203. This value can be adjusted with the standardisation (P435).

Closes

4 = Torque current limit, based on motor data settings in P203 and

P206. Signals a corresponding torque load on the motor. This
value can be adjusted with the standardisation (P435).

Closes

5 = Frequency limit, based on motor nominal frequency setting in

P201. This value can be adjusted with the standardisation (P435).

Closes

6 = Setpoint reached, indicates that the FI has completed the

frequency increase or decrease. Setpoint frequency = actual
frequency! From a difference of 1 Hz  Setpoint not reached -
contact opens.

Closes

7 = Error, general error message, error is active or not yet

acknowledged. Operational - closes

Opens

8 = Warning, general warning, a limit value was reached which could

lead to a later shutdown of the FI.

Opens

9 = Overcurrent warning: At least 130% of the nominal FI current

was supplied for 30 seconds.

Opens

10 = Motor overtemperature (warning): The motor temperature is

evaluated via a digital input. Motor is too hot. The warning is
given immediately, overheating switch-off after 2 seconds.

Opens

11 = Torque current limit/Current limit active (warning): The limiting

value in P112 or P536 has been reached. A negative value in
P435 inverts the reaction. Hysteresis = 10%.

Opens

12 = Relay via P541

– external control, the relay can be controlled

with parameter P541 (Bit 0) independently of the actual operating
status of the FI.

Closes

13 = Torque limit gen. active: Limit value in P112 was reached in the

generator range. Hysteresis = 10%.

Closes