Display

Fault

Cause

Remedy

Group

Details in
P700 / P701

E003

3.0

Inverter overcurrent

I

2

t limit has triggered e.g.. > 1.5 x I

n

for 60s (see

also P504)

Continuous overload at inverter output

3.1

Overcurrent, chopper

I

2

t limit for braking resistance has triggered

(please also note P555, P556, P557)

Avoid overcurrent in brake resistance

3.2

Overcurrent derating
Monitoring 125%

Derating (power reduction) at f < 2 Hz

125% overcurrent for 50ms

for fan drives: enable flying start (P520)

E004

4.0

Overcurrent module

Error signal from module (short duration)

Short circuit or earthing at FI output

Use external output choke (motor cable is
too long)

E005

5.0

Link circuit overvoltage

DC link voltage is too high
 Reduce energy return by means of a braking

resistance

 Extend braking time (P103)
 If necessary, set switch-off mode (P108) with

delay (not for lifting equipment)

 Extend emergency stop time (P426)

5.1

Mains overvoltage

Mains voltage is too high
 Please check (380V-20% ... 480V+10%), or

200/240V

10%

E006

6.0

Link circuit undervoltage
(Charging error)

Inverter mains/link voltage too low

Check mains voltage (380V-20% ...
480V+10%), or 200/240V

10%

6.1

Mains undervoltage

E007

7.0

Mains phase error

One of the three mains input phases was or is
interrupted.
 Check mains phases (380V-20% ...

480V+10%), or 200/240V

10%

 All three mains phases must be symmetrical.

OFF

Note:

OFF appears in the display when the three mains phases are uniformly
reduced, i.e. when a normal mains switch off occurs during operation.