NORD Drivesystems BU0750 User Manual

Page 136

Advertising
background image

NORDAC SK 750E Manual

136

Subject to technical amendments

BU 0750 GB-3311

Display

Fault

Cause

Remedy

Group

Details in
P700 / P701

E010

10.0

Telegram downtime
(P513)

Data transfer is faulty. Check P513.
 Check external Bus connection.
 Check bus protocol program process.
 Check Bus Master.
 Check 24V supply of internal CAN/CANopen

Bus.

 Nodeguarding error (internal CANopen)

Bus Off error (internal CAN Bus)

10.2

External bus module telegram
timeout

Telegram transfer is faulty.
 Check external connection.
 Check bus protocol program process.
 Check Bus Master.

10.4

External bus module initialisation
failure

 Check P746.
 Bus module not correctly plugged in.
 Check Bus module current supply.

10.1

External Bus module system
failure

Further details can be found in the respective
additional BUS operating instructions.

10.3

10.5

10.6

10.7

10.8

External module communication
error

 Connection fault / error in the external

component

E011

11.0

Reference voltage (SK CU1-...)

Reference voltage of customer unit faulty
(10V / 15V). Only displayed if control is via the
control terminals (P509 = 0/1).
 Check control terminals connection for short-

circuit.

 I/O module may not be correctly engaged.

E012

12.0

Customer Watchdog

The Watchdog function is selected at a digital
input and the impulse at the corresponding digital
input is not present for longer than the time set in
parameter P460 >Watchdog time<.