NORD Drivesystems BU0750 User Manual

Page 112

Advertising
background image

NORDAC SK 750E Manual

112

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P510

Auxiliary setpoint interface

Always visible

0 ... 8
[ 0 ]

Selection of the interface via which the FI receives the setpoint.

0 = Auto: the source of the auxiliary setpoint is

automatically derived from the setting in the parameter
P509 >Interface<

1 = Control terminals, digital and analog inputs control the

frequency, including fixed frequencies

2 = USS

3 = CAN

4 = Profibus

5 = InterBus

6 = CANopen

7 = DeviceNet

8 = Reserved

P511

USS baud rate

Always visible

0 ... 3
[ 3 ]

Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must have
the same baud rate setting.

0 = 4800 Baud

1 = 9600 Baud

2 = 19200 Baud

3 = 38400 Baud

P512

USS address

Always visible

0 ... 30
[ 0 ]

Setting of the FI Bus address.

P513

Telegram downtime

Always visible

-0.1 /

0.0 ... 100.0 s
[ 0.0 ]

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an error and switches off with the error
message E010 >Bus Time Out<.
-0.1 = 10.8 / 10.2 inactive, monitoring switched off, no error is generated.
0.0 … 100.00 s = = Response time for telegram failure

P514

CANbus baud rate

Always visible

0 ... 7
[ 4 ]

Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must
have the same baud rate setting.
Further information can be obtained from the manual BU 0060 CANbus.

0 = 10kBaud

1 = 20kBaud

2 = 50kBaud

3 = 100kBaud

4 = 125kBaud

5 = 250kBaud

6 = 500kBaud

7 = 1MBaud *

(test purposes only)

*) Reliable operation cannot be
guaranteed

P515

CANbus address

Always visible

0 ... 255
[ 50 ]

Setting for the CANbus address.

P516

Skip frequency 1

P

Always visible

0.0 ... 400.0 Hz
[ 0.0 ]

The output frequency around the frequency value (P517) set here is not shown.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.

0 = Skip frequency inactive

P517

Skip frequency range 1

P

Always visible

0.0 ... 50.0 Hz
[ 2.0 ]

Skip range for the >Skip frequency 1< P516. This frequency value is added and subtracted from the
skip frequency.
Skip frequency range 1: P516 - P517 ... P516 + P517

P518

Skip frequency 2

P

Always visible

0.0 ... 400.0 Hz
[ 0.0 ]

The output frequency around the set frequency value (P519) is skipped.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.

0 = Skip frequency inactive