8 Error messages

BU 0750 GB-3311

Subject to technical amendments

137

Display

Fault

Cause

Remedy

Group

Details in
P700 / P701

E013

13.0

Encoder error

Encoder error (only for special extension unit
Encoder/PosiCon)
 5V Sense signal not present at encoder input

13.1

Speed slip error

 The slip speed error limit was reached.
 Increase setting in P327.

13.2

Slip error switch-off monitoring

The slip error monitoring was triggered; the motor
could not follow the setpoint.
 Increase setting value for torque limit in P112.

E014

14.0

Slave check

PosiCon

– Error 1

Further details can be found in the description
BU 0710

14.1

Host check

14.2

Reference point travel error

14.3

Absolute encoder voltage
monitoring bit

14.4

Incremental encoder error

14.5

Position change and speed do not
match

14.6

Slip error between absolute and
incremental encoders

14.7

Maximum position exceeded

14.8

Minimum position undershot

E015

15.0

Incorrect software version

PosiCon

– Error 2

Further details can be found in the description
BU 0710

15.1

Watchdog PosiCon

15.2

Stack overflow PosiCon

15.3

Stack underflow PosiCon

15.4

Undefined opcode PosiCon

15.5

Protected instruction PosiCon

15.6

Illegal word access PosiCon

15.7

Illegal instruction access PosiCon

15.8

EPROM error PosiCon

E016

16.0

Motor phase error

A motor phase is not connected.
 Check P539
 Check motor connection

16.1

Motor current monitoring for
braking mode

Required exciting current not achieved at moment
of switch-on.
 Check P539
 Check motor connection

Advertising