1 installation of customer units – NORD Drivesystems BU0750 User Manual

Page 40

Advertising
background image

NORDAC SK 750E Manual

40

Subject to technical amendments

BU 0750 GB-3311

NOTE

for 5V / 15V power supplies

The customer units and special extension units have various power supplies (5V / 15V) which
can be used externally. The maximum permissible external load current is 300mA. This can be
taken from one or more power supplies. The total current must however not exceed 300mA.
All control voltages are related to a common reference potential!
Potentials AGND /0V and GND /0V are internally linked in the device.


3.3.1 Installation of customer units

1. Switch off the mains voltage, observe

the waiting period.

2. Remove the cover by unscrewing the

8 screws, noting the PE connection.

3. Using

light

pressure

push the

customer unit into the left guide rail
until it engages.

4. Remove the connector by pressing

the releases and make the necessary
connections. Then push on the
connector.

5. Replace all covers.








ATTENTION

The PE connection must be
reconnected. Otherwise the device
must not be used (see adjacent
illustration)!

WARNING

Installation must be carried out by qualified personnel only, paying particular attention to safety and
warning instructions.
Customer units must not be inserted/removed when live.
Following the insertion, replacement or removal of modules, and once the equipment has been
switched on again, this procedure is indicated with the message E017 Customer unit changed.
Restore all PE connections!