7.6 Control clamps

BU 0750 GB-3311

Subject to technical amendments

95

Parameter

Setting value / Description / Note

Parameter
set

Available with option

14 = Actual value process controller *, activates the process controller, analog input 1 is

connected to the actual value encoder (compensator, air can, flow volume meter, etc.). The
mode (0-10 V or 0/4-20 mA) is set in P401.

15 = Setpoint process controller *, as for Function 14, however, the setpoint is specified (e.g.

by a potentiometer). The actual value must be specified via a different input.

16 = Process controller lead *, adds an adjustable additional setpoint after the process

controller.

Note: Further details regarding the process controller can be found in Section 10.2

17 = Reserved
18 = Curve travel control, the slave communicates its actual speed to the master

*) The limits of these values are set by the parameters >Minimum frequency auxiliary setpoints<
P410 and >Maximum frequency auxiliary setpoints< P411.

P401

Analog input mode 1

BSC

STD

MLT

0...3
[ 0 ]

0 = 0

– 10V limited: An analog setpoint smaller than the programmed adjustment 0% (P402)

does not lead to undershooting of the programmed minimum frequency (P104). This therefore
does not lead to a reversal of the direction of rotation.

1 = 0 - 10V: also allows output frequencies which are below the programmed minimum frequency

(P104) if a setpoint is present, which is smaller than the programmed matching of 0% (P402).
This allows reversal of the direction of rotation using a simple voltage source and
potentiometer.
E.g. internal setpoint with reversal of direction of rotation: P402 = 5V, P104 = 0Hz,
Potentiometer 0

–10V

Rotation direction change at 5V in mid-range setting of the

potentiometer.

2 = 0 – 10V monitored: If the minimum

adjusted setpoint (P402) is undershot by
10% of the difference value from P403
and P402, the FI output switches off As
soon as the setpoint is greater than
[P402 - (10% * (P403 - P402))] it delivers
an output signal again.

E.g. setpoint 4-20mA:
P402: Adjustment 0% = 1V; P403:
Adjustment 100% = 5V; -10%
corresponds to -0.4V; i.e. 1...5V
(4...20mA) normal operating zone,
0.6...1V = minimum frequency
setpoint, below 0.6V (2.4mA) output
switches off.

f / Hz

P104

(fmin)

P105

(fmax)

P

4

0

3

=

1

0

.0

V

P

4

0

2

=

2

.0

V

= 8.0V

U/V

O

F

F

=

2

.0

V

-

1

0

%

*

8

.0

V

=

1

.2

V