7.4 Motor data / characteristic curve parameters

BU 0750 GB-3311

Subject to technical amendments

87

7.4 Motor data / characteristic curve parameters

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P200

Motor list

P

Always visible

0 ... 32

[ 0 ]

The factory settings for the motor data can be edited with this parameter. The factory setting in
parameters P201...P209 is a 4-pole DS standard motor with the nominal FI power setting.
By selecting one of the possible digits and pressing the ENTER key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a 4-
pole DS standard motor.

0 = No change to data

1 = No motor: In this setting, the FI operates without current control, slip compensation and

pre-magnetising time, and is therefore not recommended for motor applications. Possible
applications are induction furnaces or other applications with coils and transformers. The
following motor data is set here: 50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos

=0.90 /

Stern / R

S

0,01

/ I

LEER

6.5A

2 = 0.25kW

3 = 0.37kW

4 = 0.55kW

5 = 0.75kW

6 = 1.10kW

7 = 1.50kW

8 = 2.2kW

9 = 3.0kW

10 = 4.0kW

11 = 5.5kW

12 = 7.5kW

13 = 11kW

14 = 15kW

15 = 18.5kW

16 = 22kW

17 = 30kW

18 = 0.25hp

19 = 0.50hp

20 = 0.75hp

21 = 1.00hp

22 = 1.50hp

23 = 2.00hp

24 = 3.00hp

25 = 5.0hp

26 = 7.5hp

27 = 10hp

28 = 15hp

29 = 20hp

30 = 25hp

31 = 30hp

32 = 40hp

Note:

As P200 returns to = 0 after the input confirmation, the control of the set motor can be
implemented via parameter P205.

P201

Nominal frequency

P

Always visible

20.0..00.3990.9 Hz

[

]

The motor nominal frequency determines the V/f break point at which the FI supplies the nominal
voltage (P204) at the output.

P202

Nominal speed

P

Always visible

300..0.24000 rpm

[

]

The nominal motor speed is important for the correct calculation and control of the motor slip and
the speed display (P001 = 1).

P203

Nominal current

P

Always visible

0.1..00.5400.0 A

[

]

The nominal motor current is a decisive parameter for the current vector control.

P204

Nominal voltage

P

Always visible

100..0.800 V

[

]

The >Nominal voltage< matches the mains voltage to the motor voltage. In combination with the
nominal frequency, this produces the voltage/frequency characteristic curve.

P205

Nominal power

P

Always visible

0.00... 315.00 kW

[

]

The motor nominal power controls the motor set via P200.

P206

cos

P

Always visible

0.50...0.90

[

]

The motor cos

is a decisive parameter for the current vector control.

These setting values depend on the selection in parameter P200.