2 process controller parameter settings – NORD Drivesystems BU0750 User Manual

Page 147

Advertising
background image

10 Additional information

BU 0750 GB-3311

Subject to technical amendments

147

10.3.2 Process controller parameter settings

(Example: Setpoint frequency: 50 Hz, control limits: +/- 25%)

P105 (maximum frequency) [Hz]

:

 

 

 

100%

%

P415

Hz

freq.

Setpoint

Hz

freq.

Setpoint

: Example

%

100

%

25

50

50

Hz

Hz

62.5 Hz

P400 (Funct. analog input)

:

„4“ (frequency addition)

P411 (setpoint frequency) [Hz]

: Setpoint frequency with 10 V at analog input 1

: Example 50 Hz

P412 (Process controller setpoint) : CR middle position / Default setting 5 V (adjust if necessary)

P413 (P controller) [%]

: Factory setting 10% (adjust if necessary)

P414 (I-controller) [% / ms]

: recommended 0.1

ms

%

P415 (limitation +/-) [%]

: Controller limitation (see above)

Note: In the function process controller, parameter P415 is used as a

controller limiter downstream from the PI controller. This parameter
therefore has a double function.

Example 25% of setpoint

P416 (ramp before controller) [s]

: Factory setting 2s (if necessary, adjust to match controller behaviour)

P420 (Funct. digital input 1)

: "1" Enable right

P421 (Funct. Digital input 2)

:

„40“ actual value PID process controller

Alternatively, the 2nd analog input (P405=14) of the
multi I/O can be used.