7.4 Motor data / characteristic curve parameters

BU 0750 GB-3311

Subject to technical amendments

89

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P214

Lead torque

P

Always visible

-200 ... 200 %
[ 0 ]

This function allows a value for the expected torque requirement to be set in the controller. This
function can be used in lifting applications for a better load transfer during start-up.
Note:

With a field of rotation to the right, the motor torques are entered with a positive
sign. Generator torques are entered with a negative sign. For rotation field to the
left, the reverse applies.

P215

Boost precontrol

P

Always visible

0 ... 200 %
[ 0 ]

Only with linear characteristic curve (P211 = 0% and P212 = 0%).
For drives that require a high starting torque, this parameter provides an option for switching in an
additional current during the start phase. The application time is limited and can be selected in the
parameter >Time boost precontrol< P216.

All current and torque current limits that may have been set (P112 and P536, P537) are
deactivated during the boost lead time.

Note:

With active ISD control (P211 and / or P212 ≠ 0%), parameterisation of P215 ≠ 0
results in incorrect control.

P216

Time boost precontrol

P

Always visible

0.0 ... 10.0 s
[ 0 ]

Only with linear characteristic curve (P211 = 0% and P212 = 0%).
Application time for increased starting current.
Note:

With active ISD control (P211 and / or P212 ≠ 0%), parameterisation of P216 ≠ 0
results in incorrect control.

P2xx

Control/characteristic curve parameters

P211

P210

P204

P201

P216

P215

Ausgangs-

spannung

Ausgangsfrequenz

Zeit

Note:

"Typical" setting for the:

Current vector control (factory setting)

P201 to P209 = Motor data

P210 = 100%

P211 = 100%

P212 = 100%

P213 = 100%

P214 = 0%

P215 = no significance

P216 = no significance

Linear V/f characteristic curve

P201 to P209 = Motor data
P210 = 100% (static boost)
P211 = 0%
P212 = 0%
P213 = no significance
P214 = no significance
P215 = 0% (dynamic boost)
P216 = 0s (time dyn. boost)