7.9 Information

BU 0750 GB-3311

Subject to technical amendments

121

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P706

.. - 01

...

.. - 05

Parameter set, last error 1...5

Always visible

0 ... 3

This parameter stores the parameter set code that was active when the error occurred. Data for
the previous 5 faults are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.

P707

.. - 01

.. - 02

Software version

Always visible

0 ... 9999

This parameter shows the software and revision
numbers in the FI. This can be significant when
different FIs are assigned the same settings.

... - 01 = Version number (3.1)
... - 02 = Revision number (1.0)

P708

Status of digital inputs

Always visible

00 ... 3F

(hexadecimal)

Displays the status of the digital inputs in hexadecimal code. This display can be used to check
the input signals.

Bit 0 = Digital input 1 [far right]

Bit 1 = Digital input 2

Bit 2 = Digital input 3

Bit 3 = Digital input 4

Bit 4 = Digital input 5

Bit 5 = Digital input 6

Bit 6 = Digital input 7 (only with PosiCon)

Bit 7 = Digital input 8 (only with PosiCon)

Bit 8 = Digital input 9 (only with PosiCon)

Bit 9 = Digital input 10 (only with PosiCon)

Bit 10 = Digital input 11 (only with PosiCon)

Bit 11 = Digital input 12 (only with PosiCon)

Bit 12 = Digital input 13 (only with encoder)

ControlBox: If there are only four digital inputs, the status is indicated in binary code. If the

Customer Unit Multi I/O, Encoder or PosiCon is installed (Bit 4, 5 ...), the display
is coded in hexadecimal.

P709

Voltage analog input 1

BSC

STD

MLT

-10.0 ... 10.0 V

Displays the measured analog input value 1. (-10.0 ... 10.0V)

P710

Voltage analog output 1

STD

MLT

0.0 ... 10.0V

Displays the value which is output from analog output 1. (0.0 ... 10.0V)

P711

Status multifunction relay

Always visible

00 ... 11 (binary)

Displays the actual status of the signal relays.

Bit 0 = Relay 1

Bit 1 = Relay 2

Bit 2 = Relay 3 (only with PosiCon option)

Bit 3 = Relay 4 (only with PosiCon option)

P712

Voltage analog input 2

MLT

-10.0 ... 10.0 V

Displays the measured analog input value 2. (-10.0 ... 10.0V)

P713

Voltage analog output 2

MLT

0.0 ... 10.0V

Displays the value which is output from analog output 2. (0.0 ... 10.0V)

P714

Operating time

Always visible

0.0 ... 9999 h

This parameter shows the time for which the FI was connected to the mains and was ready for
operation.