9 technical data, 1 general data – NORD Drivesystems BU0750 User Manual

Page 139

Advertising
background image

9 Technical data

BU 0750 GB-3311

Subject to technical amendments

139

9 Technical data

9.1 General Data

Function

Specification

Output frequency

0.0 ... 400.0Hz

Pulse frequency

3.0 ... 16.0kHz (Standard = 6kHz)

Typical overload capacity

150% for 60s, peak value 200% for 3.5s

Protective measures against

Overtemperature

of

the

frequency

inverter
Over and under-voltage

Short-circuit, earth fault
Overload, idle running

Regulation and control

Sensorless current vector control (ISD)
Field-orientated control

Linear V/f characteristic curve

Setpoint input analog / PID input
(optional)

0 ... 10V,

10V, 0/4 ... 20mA

Analog setpoint resolution

10 bit based on measurement range

Analog output

0 ... 10V scaleable (optional)

Setpoint consistency

analog < 1%

digital < 0.02% (optional)

Motor temperature monitoring

I

2

t-motor (UL/CUL certified), PTC / Bimetal switch (optional, not UL/CUL)

Ramp times

0 ... 320s

Control outputs (optional)

1 or 2 relays 28V DC / 230V AC, 2A

Interface (optional)

According to option:
RS 485 (standard)

CANbus
CANopen
DeviceNet

Profibus DP
InterBus
AS interface

Efficiency of frequency inverter

approx. 95%

Ambient temperature

0°C ... +50°C (S1 mode), 0°C ... +60°C (S3 mode) without condensation

Storage and transport temperature

-25°C ... +60/70°C

Long-term storage

See Section 10.6.1

Protection class

IP54 air cooled version / IP65 water cooled version

Electrical isolation

Control terminals (digital and analog inputs)

Max. installation altitude above sea level

Up to 1000m:

No power reduction

1000...4000m:

1%/ 100m power reduction (up to 2000m overvoltage
cat. 3)

2000...4000m:

Only overvoltage category 2 is complied with, external
overvoltage protection at the mains input is necessary

Waiting time between two mains switching
cycles

60 sec for all devices in normal operating cycle

Ambient conditions

Transport (IEC 60721-3-2):

Vibration: 2M2

Operation (IEC 60721-3-3):

Vibration: 3M7;

Climate: 3K3

Certifications

CE, UL, cUL

Advertising