NORDAC SK 750E Manual

98

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P412

Process controller setpoint

P

Always visible

0.0 ... 10.0 V
[ 5.0 ]

Fixed specification of a setpoint for the process controller that will only occasionally be altered.
Only with P400 = 14 ... 16 (process controller). Further details can be found in Chap. 10.2

P413

PID control P-component

P

Always visible

0 ... 400.0 %
[ 10.0 ]

Only effective if the function Actual frequency PID is selected.
The P-component of the PID controller determines the frequency jump if there is a control deviation
based on the control difference.
E.g.: At a setting of P413 = 10% and a rcontrol difference of 50%, 5% is added to the actual
setpoint.

P414

PID control I-component

P

Always visible

0 ... 300.0 %/ ms
[ 1.0 ]

Only effective if the function actual frequency PID is selected.

The I-component of the PID controller determines the frequency change, dependent on time.

P415

PID control D-component

P

Always visible

0 ... 400.0 %ms
[ 1.0 ]

Only effective if the function actual frequency PID is selected.

If there is a rule deviation, the D-component of the PID controller determines the frequency change
multiplied by time (%ms).
If one of the analog inputs is set in the function actual value process controller, this parameter
determines the controller limitation (%) after the PI controller. For further details, see Section 10.2.

P416

Ramp PID controller

P

Always visible

0 ... 99.99s
[ 2.00 ]

Only effective if the function actual frequency PID is selected.
Ramp for PID setpoint


Note: Further details about the PID and process controller can be found in Section 10.2 and 10.3

P417

Offset analog output 1

P

STD

MLT

-10.0 ... +10.0 V
[ 0.0 ]

In the analog output function an offset can be entered to simplify the processing of the analog signal
in other equipment.
If the analog output has been programmed with a digital function, then the difference between the
switch-on point and the switch-off point can be set in this parameter (hysteresis).