7.6 Control clamps

BU 0750 GB-3311

Subject to technical amendments

97

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P404

Filter analog input 1

BSC

STD

MLT

10 ... 400 ms
[ 100 ]

Adjustable digital low-pass filter for the analog signal.
Interference peaks are hidden, the reaction time is extended.

P405

Analog input function 2

MLT

0...18
[ 0 ]

This parameter is identical to P400.

P406

Analog input mode 2

MLT

0...3
[ 0 ]

0 = 0 – 10V limited
1 = 0 – 10V
2 = 0 – 10V monitored
3 = - 10V – 10V


This parameter is identical to P401. P402/403 change to P407/408.

P407

Analog input adjustment 2 0%

MLT

-50.0..00.500.0 V
[ 0.0 ]

This parameter is identical to P402.

P408

Analog input adjustment 2 100%

MLT

-50.0...50.0 V
[ 10.0 ]

This parameter is identical to P403.

P409

Filter analog input 2

MLT

10 ... 400 ms
[ 100 ]

This parameter is identical to P404.

P410

Minimum frequency auxiliary setpoints

P

Always visible

-400.0..0.4000.0
Hz
[ 0.0 ]

The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:

Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Process controller

Min. frequency above analog setpoint (potentiometer)

P411

Maximum frequency auxiliary setpoints

P

Always visible

-400.0..0.4000.0
Hz
[ 50.0 ]

The maximum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:

Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Max. frequency above analog setpoint (potentiometer)

Process controller