4.6 ParameterBox error messages

Display

Fault

Cause

Remedy

Communication error

200

Illegal parameter number

These error messages are due to EMC interference or
differing software versions of the participants.

Check the software version of the ParameterBox and
that of the connected frequency inverter.

Check the cabling of all components, regarding
possible EMC interference

201

Parameter value cannot be
changed

202

Parameter outside of value
range

203

Incorrect
Sub-index

204

No Array parameter

205

Incorrect parameter type

206

Incorrect response
identifier

USS interface

207

Checksum error of USS
interface

Communication between frequency inverter and ParameterBox is
faulty (EMC), safe operation cannot be guaranteed.

Check the connection to the frequency inverter. Use a
shielded cable between the devices. Route the BUS
leads separately from the motor cables.

208

Incorrect status identifier,
USS interface

Communication between frequency inverter and ParameterBox is
faulty (EMC), safe operation cannot be guaranteed.

Check the connection to the frequency inverter. Use a
shielded cable between the devices. Route the BUS
leads separately from the motor cables.

209_1

Inverter not responding

The ParameterBox is waiting for a response from the connected
frequency inverter. The waiting time has elapsed without a response
being received.

Check the connection to the frequency inverter. The
settings of the USS parameters for the frequency
inverter were changed during operation.

Identification errors

220

Unknown device

Device ID not found.
The connected inverter is not listed in the database of the
ParameterBox; no communication can be established.

Please contact your Getriebebau Nord Representative.

221

Software version not
recognised

Software version not found!
The software of the connected frequency inverter is not listed in the
ParameterBox database, no communication can be set up.

Please contact your Getriebebau Nord Representative.

Advertising