Parameter

Setting value / Description / Note

Parameter
set

Available with option

P543

Actual bus value 1

P

Always visible

0 ... 12
[ 1 ]

The return value 1 can be selected for bus actuation in this parameter.
Note: Further details can be found in the respective BUS instruction manuals.

0 = Off

1 = Actual frequency

2 = Actual speed

3 = Current

4 = Torque current (100% = P112)

5 = Status of digital inputs and outputs

2

6 = Actual position (only with PosiCon, SK 700E)

7 = Actual position (only with PosiCon, SK 750E)

8 = Setpoint frequency

9 = Error number

10 = Actual position increment

3

(only with PosiCon, SK 750E)

11 = Setpoint position increment

3

(only with PosiCon, SK 750E)

12 =

Bus I/O Out Bits 0 … 7

P544

Actual bus value 2

P

Always visible

0 ... 12
[ 0 ]

In this parameter zhe return value 2 can be selected for bus control.
Note: Further details can be found in the respective BUS instruction manuals.

This parameter is identical to P543.

P545

Actual bus value 3

P

Always visible

0 ... 12
[ 0 ]

In this parameter zhe return value 3 can be selected for bus control. This is only available if
P546

3.

Note: Further details can be found in the respective BUS instruction manuals.

This parameter is identical to P543.

3

Assignment of the digital inputs in P543/ 544/ 545 = 5 for SK 750E

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = DigIn 5

Bit 5 = DigIn 6

Bit 6 = DigIn 7 (POS or ENC)

Bit 7 = DigIn 8

Bit 8 = DigIn 9 (POS)

Bit 9 = DigIn 9 (POS)

Bit 10 = DigIn 10 (POS)

Bit 11 = DigIn 12 (POS)

Bit 12 = Rel 1

Bit 13 = Rel 2

Bit 14 = Rel 3 (POS)

Bit 15 = Rel 4 (POS)

2

The setpoint/actual position corresponding to an 8192 increment encoder.