NORDAC SK 750E Manual

110

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P505

Absolute minimum frequency

P

Always visible

0.0 ... 10.0 Hz
[ 2.0 ]

States the frequency value that cannot be undershot by the FI. If the setpoint becomes smaller than
the absolute minimum frequency, the FI switches off or changes to 0.0Hz.
At the absolute minimum frequency, braking control (P434 or P441) and the setpoint delay (P107)
are actuated. If a setting value of "Zero" is selected, the brake relay does not switch during
reversing.
When controlling lifting equipment, this value should be set at a minimum of 2Hz. From 2Hz and
higher, the current control of the FI operates and a connected motor can supply sufficient torque.

P506

Automatic error acknowledgement

Always visible

0 ... 7
[ 0 ]

In addition to the manual error acknowledgement, an automatic one can also be selected.

0 =

No automatic error acknowledgement.

1 ... 5 = Numberof permissible automatic malfunction acknowledgments within one mains-on

cycle. After mains off and switch on again, the full number is available again.

6 =

Always, an error message will always be acknowledged automatically if the cause of the
error is no longer present.

7 =

ENTER key, acknowledgement is only possible using the ENTER key or by mains switch-
off. No acknowledgement is implemented by removing the enable!

P507

PPO type

Always visible

1 ... 4
[ 1 ]

Only with the technology unit Profibus, DeviceNet or InterBus
See also additional descriptions BU 0020, BU 0080, BU 0070

P508

Profibus address

Always visible

1 ... 126
[ 1 ]

Profibus address, only with the Profibus technology unit
See also the additional description for the Profibus control