3.3.5 Multi I/O Customer Unit

(SK CU1-MLT, Part No.: 278200010)

The Multi I/O (Customer Unit)provides the highest functionality of
digital and analog signal processing. There are 2 differential
analog input and 6 digital inputs available for control of the
frequency inverter. Both analog inputs can process signals from
0...10V, 0...20mA (4...20mA) or

-

10V...+10V.

Two programmable and scaleable analog outputs 0...10V enable
actual operating parameters to be transmitted to a display device
or process control system.
Via the two relay contacts, a brake control can be actuated or
warnings can be transferred to another system.
The digital inputs of the multi I/O cannot process analog setpoints!
(See also Section "Control terminals", P420-P425)




























NOTE: All control voltages are based on a common reference potential!

Potentials AGND /0V and GND /0V are internally linked in the device.

The maximum total current 5/15V is 300mA!

X

2

.1

X

2

.2

X

2

.3

11 VREF 10V
12 AGND /0V
14 AIN1 +

16 AIN2 +
17 AOUT1

21 DIG IN 1
22 DIG IN 2
23 DIG IN 3

24 DIG IN 4

42 VO +15V

01 REL1.1

02 REL1.2

03 REL2.1

04 REL2.2

25 DIG IN 5

26 DIG IN 6

18 AOUT2
40 GND /0V

41 VO +5V

Floating contacts or
output of a PLC: 7.5...33V

Analog inputs 1 and 2:

-10..+10V, 0/4...20mA

Analog outputs 1 and 2:

0...10V / max. 5mA

Only DIG IN 6 =

Temperature sensor!

Switching threshold = 2.5 V

Digital inputs:

DIG IN 1 = On right

DIG IN 2 = On left

DIG IN 3 = parameter set bit 0

DIG IN 4 = fixed frequency 1

DIG IN 5 / 6 = No function

Additional burden resistance for 0/4...20mA

analog input 1 (250

)

Additional burden resistance for 0/4...20mA

analog input 2 (250

)

Analog PLC output:

0...10V / -10...+10 V

or Potentiometer: 2...10k

Connector Functions

Maximum cross-section Parameter

X2.1

Output relay

1.5 mm

2

P434 ... P443

X2.2

Analog signals
IN / OUT

1.0 mm

2

P400 ... P419

X2.3

Digital inputs

1.0 mm

2

P420 ... P425

Analog input 1

ON = Current,

OFF = Voltage

Analog input 2

ON = Current,

OFF = Voltage

ON OFF

U/I switching, R = 250 Ω