7.5 Speed control

BU 0750 GB-3311

Subject to technical amendments

93

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P330

Digital input 13

P

ENC

0 … 3

[ 0 ]

0 =

Off: No function, input is switched off.

1 =

Servo mode On / Off: Activation and deactivation of the Servo mode using an
external signal (High level = active). For this P300 must be set as 1 (Servo mode
= On).

2 =

Sense monitoring: A connected incremental encoder which produces a fault
signal and indicates fault functions e.g. break in the supply line or light source
failure The FI shows Error 13, Encoder error, if there is an error.

3 =

PTC resistor input: Analog evaluation of the actual signal switching threshold,
approx. 2.5 Volt.