4.3 ParameterBox Installation Version, SK PAR-2E

BU 0750 GB-3311

Subject to technical amendments

59

4.3.1 Electrical connection

The ParameterBox SK PAR-2E is connected via the screw terminal block.

Number

Description

Terminals

1

+ 4.5V ... 30V

with +15V / 60mA

0.14 ... 1.5 mm²

2

GND

3

P+ (A) RS485 +

4

P- (B) RS485 -


Supply voltage
The +15V supply voltage for the ParameterBox can normally be drawn from the connected frequency inverter.
However, if several frequency inverters are linked together, ensure that only one frequency inverter is tapped
for voltage and not several inverters! The frequency inverter with the shortest cable distance to the
ParameterBox should be selected for this.


Communication via RS485
With connection of several frequency inverters in series (as illustrated below), ensure that the ParameterBox is
the first or last participant in the bus system. A termination resistor (approx. 120

) must be provided for the

frequency inverter at the other end of the entire bus system.

Control cabinet

Gear unit motor with FI in field

SK PAR-2E

Part. No.

278910110

SK 700E

SK 750E

SK 500E

NOTE:

For further information, refer to the ParameterBox instruction manual BU 0040 GB.

Cutout in

control cabinet

door

p-box

vector

upper section

Control
cabinet door

Advertising