NORDAC SK 750E Manual

96

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter
set

Available with option

3 = - 10V – 10V: If a setpoint smaller than the programmed adjustment 0% (P402) is present, this

may cause a change in the direction of rotation. This allows reversal of the direction of rotation
using a simple voltage source and potentiometer.

E.g. internal setpoint with reversal of direction of rotation: P402 = 5V, P104 = 0Hz,
Potentiometer 0

–10V

Rotation direction change at 5V in mid-range setting of the

potentiometer.

At the moment of reversal (hysteresis =

P505), the drive stands still when the minimum

frequency (P104) is smaller than the absolute minimum frequency (P505). A brake which is
controlled by the FI has not been applied in the hysteresis range.
If the minimum frequency (P104) is greater than the absolute minimum frequency (P505),
the drive reverses when the minimum frequency is reached. In the hysteresis range

P104,

the FI supplies the minimum frequency (P104), the brake controlled by the FI is not applied.

P402

Analog input adjustment 1 0%

BSC

STD

MLT

-50.0..00.500.0 V
[ 0.0 ]

This parameter sets the voltage, which is to correspond with the minimum value of the selected
function of analog input 1.

In the factory setting (setpoint) this value corresponds to the setpoint which is set by P104
>Minimum frequency<.
Typical setpoints and corresponding settings:

0

– 10V

0.0 V

2

– 10 V

2.0 V (for function 0-10 V monitored)

0

– 20 mA

0.0 V (internal resistance approx. 250

)

4

– 20 mA

1.0 V (internal resistance approx. 250

)

P403

Analog input adjustment 1 100%

BSC

STD

MLT

-50.0..00.500.0 V
[ 10.0 ]

This parameter sets the voltage, which is to correspond with the maximum value of the selected
function of analog input 1.

In the factory setting (setpoint) this value corresponds to the setpoint which is set by P105
>Maximum frequency<.

Typical setpoints and corresponding settings:

0

– 10 V

10.0 V

2

– 10 V

10.0 V (for function 0-10 V monitored)

0

– 20 mA

5.0 V (internal resistance approx. 250

)

4

– 20 mA

5.0 V (internal resistance approx. 250

)

P400 ... P403

P401 = 0

0

–10V limited

0.0V

2.5V

5.0V

10.0V

P105

P104

P402

P403

output

frequency

setpoint

voltage

positive

P401 = 1

0

–10V not limited

0.0V

2.5V

5.0V

10.0V

P105

P104

P402

P403

output

frequency

setpoint

voltage

positive

negative