6. Electrical installation

106

Festo.P.BE-CMMS-ST-G2-HW-EN

1008NH

6.4

Interfaces

6.4.1 I/O interface [X1]

Mode switching allows assignment of the [X1] interface more than once.
As a result, a maximum of four different I/O assignments can be selected.

Mode DIN9

DIN12

Table

Mode 0 – Positioning

0

0

Table

6.2

Mode 1 – Jog mode

0

1

Table

6.3

Mode 2 – Record linking

1

0

Table

6.4

Mode 3 – Synchronisation

1

1

Table

6.5

Table

6.1 Mode switching

Pin

Name

Value

Mode = 0 - Positioning

1

AGND

0 V

Screen for analogue signals

2

AIN0

±10 V

Setpoint input 0, differential, maximum 30 V input voltage

3 DIN10

Record

selection 4 (high active)

4

+VREF

+10 V ±4%

Reference output for setpoint potentiometer

5 Unassigned

6

GND24

Reference potential for digital inputs and outputs

7

DIN1

Record selection 1 (high active)

8

DIN3

Record selection 3 (high active)

9

DIN5

Controller enable (high active)

10

DIN7

Limit switch 1

11 DIN9

High-speed

input

12

DOUT1

24 V 100 mA Output freely programmable – Default: Motion complete (high active)

13

DOUT3

24 V 100 mA Output freely programmable – Default: Error (low active)

14

AGND

0 V

Reference potential for the analogue signals

15

DIN13

Ri = 20k

Stop input (low active)

16 DIN11

Record

selection 5 (high active)

17

AMON0

0...10 V ±4% Analogue monitor output 0

18

+ 24 V

24 V 100 mA 24 V supply carried out

19

DIN0

Record selection 0 (high active)

20

DIN2

Record selection 2 (high active)

21

DIN4

End stage enable (high active)

22

DIN6

Limit switch 0

23

DIN8

Start for the positioning procedure