3. Product description

34

Festo.P.BE-CMMS-ST-G2-HW-EN

1008NH

To be able to operate an interface with a terminal program, such as for test purposes, the
following settings are required (recommendations):

Parameters Value

Flow control

None

Emulation VT100

ASCII configuration

- Sent characters finish with line feed
- Output entered characters locally (local echo)
- During reception, attach line feed to the end of the line

Table

3.7 Setting for terminal program

Please note that, immediately after a reset, the motor controller independently issues a
bootup message via the serial interface. A reception program on the controller must either
process or reject these received characters.

General commands

Command Syntax

Response

New initialisation of the positioning controller

RESET!

None (bootup message)

Save the current parameter set and all position sets in
the non-volatile flash memory.

SAVE! DONE

Setting the baud rate for serial communication BAUD9600

BAUD19200
BAUD38400
BAUD57600
BAUD115200

Unknown command

Any

ERROR!

Read the version number of the CM (Configuration
Management) release of the firmware

VERSION? 2300:VERSION:MMMM.SSSS*)

*)MMMM:

Main version of the CM release (hexadecimal format)

SSSS:

Subversion of the CM release (hexadecimal format)

Table

3.8 General commands

Parameter commands

The exchange of parameters and data takes place over “communication objects” (CO).
They are used in a fixed syntax. Special return values are defined for errors in a write or
read access.