4. Functional safety engineering

96

Festo.P.BE-CMMS-ST-G2-HW-EN

1008NH

Fig.

4.8 FCT mask for configuration of the measurement data

The two speed values are now immediately recorded for 2.55 s as soon as you actuate the

button. During this time, you remove the controller enable and so determine

the brake time from the measurement curve. This is stored under the point “Measurement
data”.

Note
FCT PlugIn version V1.0
The maximum time until the drive is at speed = 0 after the
controller enable is removed is 499.2 ms. If this time is exceeded,
the Quick Stop delay must be set to a higher value.

FCT PlugIn version V1.1
The maximum time until the drive is at speed = 0 after the
controller enable is removed can be set using the “Maximum
switch-off delay” from 2 … 10000 ms.