8. Service functions and error messages

Festo.P.BE-CMMS-ST-G2-HW-EN 1008NH

123

Error message
Main
index

Sub-
index

Meaning of error
message

Measures Error

reaction

0

5V supply fault

1

Fault in 24V supply
16V <U24V <32V = OK,
otherwise NOK

05

2

Fault in 12V supply
11V <U12V <13V = OK,
otherwise NOK

Disconnect the device from all peripherals
and check whether the error is still there
after resetting. If yes, then there is an
internal defect and repair by the
manufacturer is necessary.

PS off

06

0

Overcurrent of the
intermediate
circuit/power stage

Motor defective?
Short-circuit in cable?
End stage defective?

PS off

07 0 Overvoltage

in

intermediate circuit

Check design (application).

PS off

08

2

Encoder supply fault

4V <U_encoder <6V = OK, otherwise NOK

PS off

11 1 Error

during

homing Homing was interrupted, e.g. by

withdrawal of controller enable or by a
limit switch.

12

2

CAN communication error Common error:

1. Error when sending a message (e.g. no
bus connected)
2. Timeout when receiving the SYNC
messages in interpolated position mode.

PS off

1)

14

9

Motor identification fault Error when automatically determining the

motor parameters.

2

Initialisation fault

Error initialising the default parameters.

16

3 Unexpected

status/programming
error

The software went into an unexpected
state, e.g. unknown state in the FHPP
state machine.

PS off

17 0 Following

error

limit

exceeded

Increase error window.
Acceleration parameter too large.

PS off

1)

0

Motor temperature 5℃
below maximum

The motor temperature is less than 5°C
below the parameterised maximum
temperature

Ignore

1)

18

1

End stage temperature
5℃ below maximum

The end stage temperature is greater than
80°C.

PS off

1)

19

0

I²t at 80%

Common error:
80% of the maximum I²t utilisation has
been reached by the closed-loop
controller or by the motor.

Warn

1)