Required I/O connection for record linking

The connection plan shows the switch position in the active operating state.

*) The limit switches are set by default to opener (configuration over FCT)

With removal of DIN3 “Halt record linking”, the ongoing record linking is stopped at the
current position. If DIN3 returns, the record linking is automatically continued from this
position.
With removal of DIN9 “Mode switchover”, the ongoing record linking is ended. The
ongoing position record is still run to the end.
With removal of DIN13 “Stop”, record linking is interrupted. Record linking must then be
initialised again.