4 emc-compliant wiring, 5 operation with long motor cables, Emc-compliant wiring – Festo Контроллеры двигателя CMMS-ST User Manual

Page 115: Operation with long motor cables

Advertising
background image

6. Electrical installation

Festo.P.BE-CMMS-ST-G2-HW-EN 1008NH

115

called “environments”. The “first” environment includes electricity grids connected to
residential housing. The “second” environment includes grids connected only to industrial
plants.
Without filter measures, the following applies to stepping motor controller CMMS-ST:

EMC class

Area

Compliance with EMC requirements

Interference
emission

Second environment (industrial)

Motor cable length up to 25 m

Interference
immunity

Second environment (industrial)

Regardless of motor cable length

Table

6.18 EMC requirements: Second environment

6.5.4 EMC-compliant wiring

The following must be observed for EMC-compliant installation of the drive system (see
also Chapter

6 Electrical installation, Page 101):

1. In order to minimise current leakage and losses in the motor connection cable, the

CMMS-ST stepping motor controller should be installed as close as possible to the
motor (see also Chapter

6.5.5 Operation with long motor cables, Page 115 below).

2. The motor and angle encoder cables must be screened.
3. The screen of the motor cable is fitted to the housing of the CMMS-ST stepping motor

controller (screen connection terminals). The cable screen is also always fitted to the
corresponding stepping motor controller to prevent leaked current flowing back to the
controller which caused it.

4. Signal lines must be separated as far as possible from the power cables. They should

not be routed parallel to one another. If crossovers cannot be avoided, they should be
made as close to vertical (i.e. at a 90° angle) as possible.

5. Unscreened signal and control lines should not be used. If they must be used, they

should at least be twisted.

6. Even screened lines always have short unscreened parts at either end (unless a

screened plug housing is used).

In general: - Connect the inner screens to the pins of the plug connector provided for

the purpose; length max. 40 mm.

- Max. length of unscreened wires: 35 mm.
- Connect total shield flat at the motor to the plug or motor housing;

length max. 40 mm.

6.5.5 Operation with long motor cables

For applications with long motor cables and/or if the wrong motor cables are selected
with excessive cable capacity, the filters may be subjected to thermal overload. In order to
avoid such problems, we recommend the following procedure for applications in which
long motor cables are required: