4. Functional safety engineering

Festo.P.BE-CMMS-ST-G2-HW-EN 1008NH

81

Safety function as per
EN 61800-5-2

PILZ* component

Switch-off behaviour Stop category as

per

EN 60204-1

STO Safe

torque off PNOZ X2P

(Relay outputs forced:

– 2 safety contacts no

delay

Connection options for:

– EMERGENCY OFF
pushbuttons

– Protective door limit
switches

– Start button)

0

SS1

Safe Stop 1

PNOZ XV2P

(Relay outputs forced:

– 2 safety contacts no

delay

– 2 safety contacts

relapse delayed

Connection options
identical to X2P;

Fixed or adjustable
relapse delay;

Cancelling the time delay

via Reset button)

1

*or comparable safety switch device with corresponding safety contacts

Table

4.2 Overview of the safety function in accordance with EN 61800-5-2

An overview of the various stop categories is provided by the Table

4.3.

Stop category

Type

Handling

0

Uncontrolled shutdown through
immediate switching off of the energy.

EMERGENCY OFF or EMERGENCY STOP

1

Controlled shutdown through switching
off of the energy when a standstill has
been reached.

EMERGENCY STOP

2

Controlled shutdown without switching
off the energy in standstill.

Not suitable for EMERGENCY OFF or
EMERGENCY STOP

Table

4.3 Stop categories