4. Functional safety engineering

80

Festo.P.BE-CMMS-ST-G2-HW-EN

1008NH

F1

Seldom to less often and/or the time of the exposure to hazard is short

F2

Frequent to continuous and/or the time of the exposure to hazard is long

P

Possibility to avoid the hazard or limit the damage

P1

Possible under certain conditions

P2 Scarcely

possible

Fig.

4.1 Risk graph for definition of the PL

r

Among other issues, the EN 60204-1 standard deals with the handling of emergencies and
defines the terms EMERGENCY OFF and EMERGENCY STOP (see table).

Handling

Definition (EN 60204-1)

Danger case

EMERGENCY
OFF

Electrical safety in case of emergency by
switching off the electrical energy to all or
part of the installation.

EMERGENCY OFF is to be used where a risk
of electric shock or other electrical risk
exists.

EMERGENCY
STOP

Functional safety in an emergency by
bringing a machine or movable parts to a
standstill.

EMERGENCY STOP is used to stop a process
or a motion if this creates a danger.

Table

4.1 EMERGENCY OFF and EMERGENCY STOP as per EN 60204-1

The standard EN 61800-5-2 describes various safety functions that can be used
dependent on the application.
For the position controllers of the CMMS-ST-G2 family, the STO and SS1 safety functions
have been implemented through external circuitry.