4-18

GV3000/SE AC Bookshelf Drive Software Reference, Version 6.06

P.008 Terminal Strip Speed Reference Source

(continued)

= Selection combination is acceptable.

If an optional RMI board is installed in the drive, refer to Appendix F for more
information regarding digital input configuration.

For more information about the analog input, refer to Appendix G.

Table 4.3 – Acceptable P.007 and P.008 Selection Combinations

P.007

Selections

P.008 Selections

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

8

9

10

11

12

P.007/P.008 Selection Example

If you want to select the MOP as the speed reference source, P.008 must be set to 1.
Next, select the value for P.007 using table 4.3. Following the 1 column down under
P.008 Selections, the acceptable selections for P.007 are 4, 5, 6, 7, or 12.

P.009 Terminal Strip Analog Input Offset

This parameter
allows for correcting
any offset in the
terminal strip analog
input prior to the
signal reaching the
drive.

This parameter is not
used if the terminal
strip analog input is
used as vector torque
reference
(U.000 = 1).

Parameter Range:

-900 to +900

*

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

P.000 Control Source

*

For 0 to 10 V (or -10 V to +10 V input), a value of +1 equals an offset of approximately 10 mV.

For 0 to 20 mA input, a value of +1 equals an offset of approximately 20

µ

A.