Troubleshooting the Drive Using Error Codes

5-3

5.2

Identifying Fault Codes and Recovering

GV3000/SE drive fault codes are shown in table 5.2. To clear a single fault that has
occurred so that the drive can be started again, correct any problems indicated by the
fault code and press the STOP/RESET key on the keypad, or assert the fault reset
from the selected control source (P.000). Because multiple faults can occur and only
the first will be displayed, you must access the error log in order to view all of the faults
that have occurred. See section 5.3 for instructions on how to view the error log.

!

ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait
five (5) minutes for the DC bus capacitors to discharge and then check
the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe
this precaution could result in severe bodily injury or loss of life.

Table 5.2 – List of Fault Codes

Code

Fault

Description

Fault Cause

Corrective Action

AIn

Analog input signal
loss

P.011 = 4 or 5 and 4 to 20 mA analog
input is below 2 mA.

Verify that P.011 is set correctly.

Check that the analog input source
supply

4 mA.

bYC

Incorrect precharge
status.

Precharge initiated and incorrect
status returned.

Check operation of precharge.

CHS

Default parameter
restore (checksum
error)

During drive operation:
Regulator board failure.

Contact Reliance or replace Regulator
board.

After Regulator board replacement:

Contact Reliance.

EC

Earth current failure
(ground fault)

Unintentional grounding of the output.

Check isolation between ground and
output terminals. Possible leakage,
current sensor defects; replace
sensor.

EEr

Non-volatile
memory write
failure

Failure on write to non-volatile
memory.

Connect CS3000 software to upload
parameters or record by hand. Then
replace Regulator board. Parameter
values will be lost when power is
cycled.

EL

Encoder loss

Drive is not detecting feedback from
the encoder.

Check the connection between the
encoder and the drive. Check the
encoder/motor coupling.

For SVC operation, conditions exist for
more than 5 seconds that may result in
an inability to complete a ramp-to-rest
stop.

For SVC operation, check motor data
parameters. Check U.006. Incorrect
magnetizing current may be generated
by performing self-tuning with a load
connected to the motor.

FL

Function loss

Function loss input on control terminal
is opened.

Check external interlocks at terminals
16, 20.

HId

High time
identification
aborted

Identification process for V/Hz has
been aborted.

See H.019 for identification result.

HIL

High line voltage

Input voltage more than 15% above
nominal. (Note that this is not tested
for in 1-150 HP Power Modules
configured for vector control.)

Check actual line voltage against
U.018 or H.021.