Programming Reference

4-33

The presets are configured using parameters P.007 and P.008. P.008 must be set to
values of 2 through 7 for preset speeds. See table 4.4 and figure 4.6.

P.029 Elapsed Time Meter

This parameter
displays the number
of days (24-hour
periods) that the drive
has been under
power or the time
elapsed since the
Elapsed Time Meter
Reset (P.030)
parameter was last
reset.

Parameter Range:

0 to 9999 days

Default Setting:

N/A

Parameter Type:

Read only

Refer also to parameters:

P.030 Elapsed Time Meter Reset

P.030 Elapsed Time Meter Reset

This parameter sets
parameter P.029
(Elapsed Time Meter)
and the error log
clock to zero. This
parameter is set to
OFF after the reset
operation is carried
out.

Parameter Range:

OFF = No action

ON = Reset the Elapsed Time Meter (P.029) and the

error log clock to zero (0)

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.029 Elapsed Time Meter

P.031 to P.038 Preset Speed 1 through Preset Speed 8

These parameters
allow the setting of up
to eight different
preset speeds.

Parameter Range:

Minimum Speed (P.003) to Maximum Speed (P.004)

Default Setting:

5.0 Hz (V/Hz)
150 RPM (vector)

Parameter Type:

Tunable

Refer also to parameters:

P.007 Terminal Strip Digital Inputs Configure
P.008 Terminal Strip Speed Reference Source