Programming Reference

4-39

This diagnostic detects phase loss between the drive and the motor. When the
diagnostic is enabled and output phase loss is detected, a drive fault is logged (OPL is
displayed).

The output phase loss diagnostic can be disabled to avoid nuisance faults which may
occur, for example, when a small motor is used with a large Power Module.

This parameter can compensate for acoustic noise by allowing adjustment of the
switching frequency of the transistors in the inverter bridge.

Keeping the carrier frequency at 8 kHz will ordinarily provide the quietest motor
operation.

See the GV3000/SE Bookshelf hardware reference manual for the Power Module
ratings at a 2 kHz carrier frequency. See P.095 in this chapter which displays the
maximum output current rating of the drive.

P.045 Output Phase Loss Enable

This parameter is
used to enable the
output phase loss
detection diagnostic.

Parameter Range:

OFF = Disable output phase loss diagnostic

ON = Enable output phase loss diagnostic

Default Setting:

ON

Parameter Type:

Tunable

Refer also to parameters:

N/A

P.047 Carrier Frequency (kHz)

This parameter
selects the drive’s
carrier frequency.

Parameter Range:

2 = 2 kHz carrier frequency

4 = 4 kHz carrier frequency

8 = 8 kHz carrier frequency

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Configurable

Refer also to parameters:

N/A