U.008 torque self-tune enable – Rockwell Automation GV3000/SE AC Gen. Purpose & Vector Bookshelf Drive Start-Up and Reference Manual User Manual

Page 160

Advertising
background image

4-74

GV3000/SE AC Bookshelf Drive Software Reference, Version 6.06

For FVC operation (U.001

SE

)

, this procedure determines the encoder PPR

selection for parameter U.001 (Encoder PPR). Determining the encoder PPR may be
necessary since the PPR is not always listed on the motor or encoder nameplate.
Determining the magnetizing current ratio is necessary in vector regulation so that the
proper no-load current, or magnetizing current, is set. The proper magnetizing current
is required to develop rated motor torque, speed, and horsepower in vector regulation.

For FVC and SVC operation, this procedure also determines the value for parameter
U.006 (Magnetizing Current).

This parameter will be set to OFF when self-tuning is completed or aborted. This
parameter only enables self-tuning. It does not start the procedure. Parameters U.002,
U.003, U.004, U.005, and U.007 must be programmed before enabling self-tuning in
U.008. Then the START key can be pressed to start the procedure. During the test,
the motor will accelerate up to 90% of U.005 (Motor Nameplate RPM) even if this
value is greater than the value set in P.004 (Maximum Speed).

U.008 Torque Self-Tune Enable

This parameter
enables the
self-tuning
procedure.

Parameter Range:

ON = Enable self-tuning

OFF = Disable self-tuning

Default Setting:

OFF

Parameter Type:

Configurable

Refer also to parameters:

U.001 Encoder PPR (FVC only)
U.006 Magnetizing Current

!

ATTENTION: The motor must be uncoupled from the drive load during
self-tuning operation or incorrect parameter values will result. This
includes any shaft-coupled devices such as reducers, belts, or brakes.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.