Starting Up the Drive for Vector Regulation

2-3

To Restore a Default Parameter Value after Writing over It:

If you enter the wrong value while programming parameters, you can restore the
default if you have not yet pressed the ENTER key. To do so:

1.

Press the PROG key.

2.

Press the ENTER key. The default value of the parameter will be displayed again.
You can select it with ENTER or enter a new one and press ENTER.

To Restore All the Default Values to General (P) Parameters:

If you need to restore all the default values for General (P) parameters after
programming them, you can do so using the Restore Defaults parameter (P.050).

2.2

Start-Up Procedure (Vector)

This section describes the start-up procedure for drives set up for vector regulation.
Before using this procedure, you should have read section 2.1 for information you
need to know before working with the drive.

Step 1. Power Up the Drive

This step verifies that the drive powers up and passes the power-up diagnostics. After
the drive passes the diagnostics, the keypad/display automatically enters monitor
mode with speed displayed.

Turn power on.

The initial display will show SELF,
with all monitor mode and status
LEDs on, indicating the drive is
performing power-up diagnostics.

After diagnostics are complete (5-6
seconds), the RPM LED is on and the
keypad/display is in monitor mode.
The displayed value is zero. You can
move through the six items that can
be accessed in monitor mode - RPM,
V(olts), A(mps), Hz, kW, and TRQ -
by pressing the ENTER key.