Programming Reference

4-65

H.018 Volts/Hertz Curve Type

(continued)

Figure 4.13 – Volts/Hertz Curve Selection

H.019 Identification Result

This parameter
displays the result of
the identification
procedure. Normally,
the identification
procedure will be
successful, and the
value in H.019 will
be = 0.

Parameter Range:

0 = Identification procedure successful. No fault.

1 = A logged error aborted the identification

procedure. Refer to section 5.3 for how to
determine the cause of the fault. Remove the
cause and repeat the procedure.

2 = A function loss aborted the identification

procedure. Depending on Function Loss
Response (P.026), this is or is not logged.
Remove the cause and repeat the procedure.

3 = A stop command aborted the identification

procedure. Repeat the procedure without
stopping.

4 = The identification procedure aborted because

the measured current feedback signal is too low.
Feedback signal elements or wiring is defective.
Check motor connections, inverter wiring, and
feedback devices (current sensors). Repeat
procedure.

6 = Calculation result based on identification

procedure measurements is out of range. Check
causes of incorrect measurements, such as
motor connections. Repeat procedure.

Default Setting:

0

Parameter Type:

Read only

Refer also to parameters:

H.020 Identification Request

Motor

Voltage
(H.000)

Volts

Hz

Motor

Base Frequency

(H.001)

Motor

Voltage
(H.000)

Volts

Hz

Motor

Base Frequency

(H.001)

Motor

Voltage
(H.000)

Volts

Hz

Motor

Base Frequency

(H.001)