Rockwell Automation GV3000/SE AC Gen. Purpose & Vector Bookshelf Drive Start-Up and Reference Manual User Manual

Page 51

Advertising
background image

Starting Up the Drive for Vector Regulation

2-13

Step 5.17 Press the

key to increase maximum speed or the

key to decrease

maximum speed.

The adjustment range is:

10 to Motor Top Speed (set in
parameter U.017). Refer to Step 7 for
parameter U.017.

VALUE ENTERED:

Step 5.18 Press the ENTER key to save the changed value.

After pressing ENTER, the same
parameter number is displayed. You can
now go to the next step.

Step 5.19 Press the

key until P.005, Current Limit, is displayed.

This parameter sets the stator current
limit as a percentage of motor rated
amps.

Step 5.20 Press the ENTER key to display the default setting of P.005.

This display is the default setting for
Current Limit, 150% of the value
entered in U.004.