Rockwell Automation GV3000/SE AC Gen. Purpose & Vector Bookshelf Drive Start-Up and Reference Manual User Manual

Page 198

Advertising
background image

C-2

GV3000/SE AC Bookshelf Drive Software Reference, Version 6.06

Second Menu General Parameters (USA Defaults)

Second Menu Volts/Hertz Parameters (USA Defaults)

Second Menu Vector Parameters (USA Defaults)

Parameter

No.

Parameter

Name

Power Module

150ER4060

150ET4060

240ER4060

240ET4060

300ER4060

300ET4060

430ER4060

430ET4060

P.047

Carrier Freq. (kHz)

2

2

2

2

Parameter

No.

Parameter

Name

Power Module

150ER4060

150ET4060

240ER4060

240ET4060

300ER4060

300ET4060

430ER4060

430ET4060

H.002

Motor Namepl. Amps

9.0

11.9

17.8

31.0

Parameter

No.

Parameter

Name

Power Module

150ER4060

150ET4060

240ER4060

240ET4060

300ER4060

300ET4060

430ER4060

430ET4060

U.004

Motor Namepl. Amps

11.0

13.8

20.5

20.5

U.005

Motor Namepl. RPM

1778

1777

1780

1780

U.006

Magnetizing Current

60.3

52.8

52.1

52.1

U.012

Speed Reg. Prop. Gain

5.00

5.00

5.00

5.00

U.013

Speed Reg. Int. Gain

5.00

5.00

5.00

5.00

U.014

Torque Reg. Prop.
Gain

0.40

0.40

0.40

0.40

U.015

Torque Reg. Integral
Gain

200.0

200.0

200.0

200.0

U.016

Field Weaken Start
RPM

1778

1777

1780

1780

U.017

Motor Top Speed

1778

1777

1780

1780

U.019

Flux Current Reg.
Prop. Gain

0.30

0.30

0.30

0.30

U.021

Rotor Time Constant

250

250

250

250

U.022

Motor Namepl. HP

10.0

14.0

20.0

20.0

U.032

SVC Flux Curr. Reg.
Gain

1000

950

900

900

Advertising