Starting Up the Drive for Volts/Hertz Regulation

1-3

To Restore All the Default Values to General (P) Parameters:

If you need to restore all the default values for General (P) parameters after
programming them, you can do so using the Restore Defaults parameter (P.050).

1.2

Start-Up Procedure (Volts/Hertz)

This section describes the start-up procedure for drives set up for V/Hz regulation.
Before using this procedure, you should have read section 1.1 for information you
need to know before working with the drive.

Step 1. Power Up the Drive

This step verifies that the drive powers up and passes the power-up diagnostics. After
the drive passes the diagnostics, the keypad/display automatically enters monitor
mode, with speed displayed.

Turn power on.

.

The initial display shows SELF, with all
monitor mode and status LEDs on,
indicating the drive is performing power-up
diagnostics.

After diagnostics are complete (5-6
seconds), the RPM LED is on and the
keypad/display is in monitor mode. The
displayed value is zero. You can move
through the five items accessible in monitor
mode - RPM, V(olts), A(mps), Hz, and kW -
by pressing the ENTER key.