GV3000/SE AC Bookshelf Drive Software Reference, Version 6.06

Important: The stop input on the terminal strip is not active when the Control Source

parameter (P.000) is set to LOCL, as it is during this start-up procedure.
Use the STOP/RESET key if you need to stop the drive.

Step 7. Check Motor Rotation Direction

This step involves verifying the speed reference is set to minimum speed, starting the
drive, and checking that the motor rotates in the correct direction. It is performed with
the motor disconnected from the load.

!

ATTENTION: The subsequent steps require rotating parts and/or
electrical circuits to be exposed. Stay clear if unit must be running, or
disconnect and lock out or tag power source if contact must be made.
Failure to observe this precaution could result in severe bodily injury or
loss of life.

Step 7.1 Press the PROG key until the PROG LED turns off.

The keypad/display will enter monitor
mode.

Step 7.2 Verify that the AUTO LED is off (press the AUTO/MAN key until the AUTO

LED turns off).

This selects the local keypad as the
speed reference source.

Step 7.3 Press the

key or the

key once.

The monitor mode LEDs will all turn off
and the manual speed reference value
will be displayed. The speed reference
value is in the units defined in P.028.
The display shown here is only an
example.

Step 7.4 If the speed reference is at minimum speed, then proceed to step 7.6.

If the speed reference is not at minimum speed, proceed to step 7.5.