Starting Up the Drive for Volts/Hertz Regulation

1-17

Step 5.19 Press the ENTER key.

The default setting is 0.

Step 5.20 Press the

key to increase the selection value, or leave it at 0.

If you do not have AC input or you are using a snubber resistor, see the

H.017 parameter description for more information.

The adjustment range is:

0 = AC input; snubber resistor not used;

ride-through enabled.

1 = AC input; snubber resistor used;

ride-through enabled.

2 = DC input; snubber resistor not used;

ride-through disabled.

3 = DC input; snubber resistor used;

ride-through disabled.

4 = DC input; snubber resistor not used;

ride-through enabled.

5 = DC input; snubber resistor used;

ride-through enabled.

VALUE ENTERED:

Step 5.21 Press the ENTER key to save the changed value.

After pressing ENTER, the same
parameter is displayed. You can now
move to the next parameter.