Starting Up the Drive for Vector Regulation

2-23

Step 6.26 Press the ENTER key to save the changed value.

After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.

Step 6.27 Press the

key to display U.006, Motor Magnetizing Current.

This parameter is the percent of
magnetizing current with respect to motor
rated amps.

Note that when the vector regulation
self-tuning procedure is performed (step 8),
the value of this parameter is automatically
calculated. You do not need to enter a value
now.

Step 6.28 Press the

key to display U.007, Motor Nameplate Volts.

This parameter is the Motor Nameplate
Volts and is taken from the motor
nameplate.

X

530
9

$

+]

N:

754

3$66

581

-2*

$872

):'

5(9

352*

5(0

!

ATTENTION: If this parameter is set incorrectly, overcurrent or excess
heating of the motor could result. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.