Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 103

Advertising
background image

Troubleshooting the ControlNet Module and Network

8-9

9

Online @ 500kbps

The module and DPI product are
communicating at 500 kbps.

10

Bad Host Flt

The module was connected to an incompatible
product.

11

Dup. Port Flt

Another peripheral with the same port number
is already in use.

12

Type 0 Login

The module has logged in for type 0 control.

13

Type 0 Time Flt

The module has not received a type 0 status
message within the specified time.

14

DL Login

The module has logged into a datalink.

15

DL Reject Flt

The host rejected an attempt to log in to a
datalink because the datalink is not supported
or is used by another peripheral.

16

DL Time Flt

The module has not received a datalink
message within the specified time.

17

Reserved

Not used.

18

Control Disabled

The module has sent a “Soft Control Disable”
command to the DPI product.

19

Control Enabled

The module has sent a “Soft Control Enable”
command to the DPI product.

20

Message Timeout

A Client-Server message sent by the
peripheral was not completed.

21

Flt Cfg Error

Flt Cfg for the Reference or Data links is set to
a value greater than 65535 and the drive is set
for 16-bit.

22

App CRC Flt

Start-up sequence detected corrupt
application firmware.

23

App Updated

Start-up sequence detected new application
firmware in candidate area.

24

CN Comm Flt

The module detected a fault condition on the
ControlNet network.

25

CN Sent Reset

The peripheral received a reset from the
network.

26

CN Close Fit

An I/O connection from the network to the
peripheral was closed.

27

CN Idle Flt

The peripheral is receiving “idle” packets from
the network.

28

CN Open

An I/O connection to the peripheral from the
network has been opened.

29

Net Timeout Flt

An I/O connection from the network to the
peripheral has timed out.

30

PCCC IO Close

The device sending PCCC Control messages
to the peripheral has sent the PCCC Control
Timeout to a value of zero.

Table 8.6 – Event Codes and Descriptions

Code

Event

Description

Advertising