7-23

Set_Attributes_Scattered sample request and response data:

(Source) Request Data

(Destination) Response Data

A Set_Attribute_Single message is used to write a single parameter
(figure 7.27).

A Service Code of “10” indicates the Set_Attribute_Single service
(see page C-8, Services).

A Class Name of “F” indicates the Parameter Object (see page
C-6, Parameter Object).

An Instance of “45” indicates the Drive Parameter 45 Attributes
(see page C-6, Instances).

An Attribute of “1” indicates the Parameter Value (see page C-7,
Instance Attributes).

N13:0

45

Parameter Number = 45

N13:1

50

Value = 0.50HP

N13:2

0

(Pad Word)

N13:3

44

Parameter Number = 44

N13:4

1740

Value = 1740RPM

N13:5

0

(Pad Word)

N13:6

43

Parameter Number = 43

N13:7

600

Value = 60.0Hz

N13:8

0

(Pad Word)