Troubleshooting the ControlNet Module and Network

8-5

8.1.4 NET A and B Independently

Table 8.4 – NET A and B Independently: State Definitions

Status

Cause

Corrective Actions

One
channel
LED is
steady off

That channel is
disabled or not
supported.

Program the network for
redundant media, if required.

One
channel
LED is
flashing
red/green

There is an invalid
link configuration
for that channel.

Power cycle or reset the
module.

Reset the controller.

If the problem persists, contact
Rockwell Automation support.

One
channel
LED is
flashing
red/off

The channel is not
receiving network
activity.

Check media for broken calbes,
loose connectors, missing
terminators, etc.

One
channel
LED is
flashing
green/off

A temporary
channel error has
occurred, or the
channel is in listen-
only mode.

Verify the controller is present
on the network and working.

One
channel
LED is
steady
green

Normal operation
for that channel.

No action required.