Main program (plc- 5c), 7 main program (plc-5c) – Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual
Page 58

6-8
ControlNet Communications Module
6.7
Main Program (PLC-5C)
Figure 6.3 – I/O Messaging
There is an operator station wired into the local rack as follows:
I:000/0 Start (Normally Open Pushbutton)
I:000/1 Stop (Normally Closed Pushbutton)
I:000/2 Clear Faults (Normally Open Pushbutton)
I:000/3 Forward / Reverse Selector Switch
I:001 Operator Speed Reference
O:000/0 Drive Ready
O:000/1 Drive Active
O:000/2 Drive Faulted
O:001 Operator Speed Feedback
The 20-COMM-C on the PowerFlex 70 drive is mapped as follows:
N9:0 Logic Status
N10:0 Logic Command
N9:1 Feedback
N10:1 Reference
N9:2 Datalink A1 Out
N10:2 Datalink A1 In
N9:3 Datalink A2 Out
N10:3 Datalink A2 In
N9:4 Datalink B1 Out
N10:4 Datalink B1 In
N9:5 Datalink B2 Out
N10:5 Datalink B2 In
N9:6 Datalink C1 Out
N10:6 Datalink C1 In
N9:7 Datalink C2 Out
N10:7 Datalink C2 In
N9:8 Datalink D1 Out
N10:8 Datalink D1 In
N9:9 Datalink D2 Out
N10:9 Datalink D2 In
0000
I:000
0
Operator
Start
Pushbutton
N10:0
1
Drive
Logic Command
START
0001
I:000
1
Operator
Stop
Pushbutton
N10:0
0
Drive
Logic Command
STOP
The RECOMM-CNET on the SP600 drive is mapped as follows: