Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual
Page 45
Advertising
RSNetWorx Configuration for PLC-5C Applications
5-15
Note the values in the Input Address and Output Address fields.
These are needed to develop a ladder program.
Step 10. Enter the desired Requested Packet Interval (RPI) and
note the value (figure 5.20). Ensure that this value is
equal to or greater than the value that will be set later for
Network Update Time (NUT). The Actual Packet Interval
(API) may vary from the Requested Packet Interval.
Step 11. Click the Electronic Keying tab. Electronic Keying is
used to determine the criteria used for the scanner to
establish a connection to a node. Select the settings
according to your application needs (figure 5.21).
Figure 5.20 – Communicaiton Properties
SP600
Advertising